Does a diesel storage tank need a firewall

2026-08-18 Leave a message
? Diesel Storage Tanks firewalls, dikes & spill control
mandatory firewalls · fire dikes · non‑combustible materials · spill prevention
?

Mandatory Firewalls for Indoor Storage

  • Strict requirement – when tanks are installed indoors (generator rooms, boiler rooms, workshops), they must be housed in a dedicated, independent room.
  • Fire resistance ≥ 3 hours – the room must be separated by firewalls with a fire resistance limit of no less than three hours to contain potential fires and prevent spread.
⛰️

Fire Dikes for Outdoor Tank Farms

  • Equivalent safety measure – outdoor tanks must be surrounded by non‑combustible fire dikes.
  • Physical containment – dikes act as barriers to contain fuel in the event of a tank rupture or leak, preventing uncontrolled fire spread or environmental disaster.
?

Strict Prohibition of Combustible Materials

  • Non‑combustible materials only – whether firewalls indoors or dikes outdoors, all structural materials must be strictly non‑combustible.
  • Class A finishes – interior of storage rooms must be finished with Class A non‑combustible materials; wood or any combustible materials are absolutely prohibited in the storage space or tank foundation.
?

Spill Prevention & Drainage Controls

  • Indoor anti‑spill facilities – raised thresholds or collection trenches prevent leaking diesel from escaping the storage room.
  • Outdoor dike design – must hold the volume of the largest tank; drainage pipes exiting the diked area must be equipped with water seals to prevent fire spread through the drainage system.
comply with NFPA 30 and local building codes regular inspection of fire barriers is mandatory