What are the anti-static grounding requirements for diesel storage tanks

2026-07-21 Leave a message

1. Mandatory Dual Grounding Connections

  • Tanks ≥50 m³ or diameter >2.5 m must have at least two separate grounding connections.
  • Points must be symmetrically arranged around the bottom perimeter.
  • Spacing between grounding points must not exceed 30 meters.

2. Strict Grounding Resistance Limits

  • Grounding resistance must generally not exceed 10 ohms.
  • Connections should be arranged in a closed‑loop configuration at the tank base.
  • Provides a highly reliable and redundant path for static charge dissipation.

3. Essential Bonding of Flanges & Accessories

  • All metallic components (flanges, valves, pipe joints) must be cross‑bonded for electrical continuity.
  • Top‑mounted accessories (breathing valves, safety valves, level devices) must be connected to the main tank.
  • Prevents localized static accumulation on any attached component.

4. Specialized Grounding for Floating Roofs

  • Floating roofs must be connected to the main tank body using at least two flexible copper cables.
  • Minimum cross‑sectional area: 25 mm² to accommodate continuous movement.
  • Ensures reliable static discharge path and prevents dangerous sparks.